We are not the manufacturer, authorised distributor or authorised representative of the SENECA brand in Australia. The private labels and part numbers shown on this website are the property of their respective owners.
Manufacturer
SENECA
Country
Italy
Name
K121
Category
Converters
Type
Compact converter
Description
Universal isolator converter loop powered
Stock availability:
Expected within 5 days
K121 is a versatile universal converter capable of processing all types of analog signals. It has multiple input types including Cu50, Cu100, Pt100, Pt500, Pt1000, Ni100, Ni120, Ni1000, and TC J, K, R, S, T, B, E, N, L. Its input impedance is 10 MΩ for thermocouples, resistance temperature detectors, and voltage.
Potentiometers have an input impedance of 10 MΩ and a range of 500 Ω..100 kΩ. The voltage input range is -150..+150 mV with an input impedance of 10 MΩ and -30..+30 V with an input impedance of 200 kΩ. The current input range is -24..+24mA with an impedance of 40Ω. The resistance range is 0..+400 (1.760) Ω. The maximum power dissipation of K121 is < 660 mW. It has programmable rejection for 50 or 60 Hz and an operating temperature range of -20..+65°C.
K121 can be used in various applications that require the processing of analog signals such as industrial control, instrumentation, and measurement systems. It comes with 8 spring clamps for easy and secure connection of wires. K121 can accurately convert any analog signal into a digital signal.
Overall, K121 is an excellent sensor for applications that require accurate data processing. Its versatility in processing various input types and programmable rejection rates make it highly adaptable to a wide range of applications.
POWER SUPPLY | 7..30 Vdc (da loop 4..20 mA) |
HOT SWAPPING | Yes |
MAX POWER CONSUMPTION | 24 mA |
MAX POWER DISSIPATION | < 660 mW |
INSULATION | 1,5 kVac (2 vie) |
STATUS LED | Anomaly Alarm |
ACCURACY CLASS | 0,1% |
INPUT TYPE | Cu50, Cu100 Pt100, Pt500, Pt1000 Ni100, Ni120, Ni1000 TC J, K, R, S, T, B, E, N, L; input impedance 10 MΩ Potentiometer: 500 Ω..100 kΩ Voltage: -150..+150 mV; input impedance 10 MΩ Voltage: -30..+30 V; input impedance 200 kΩ Current: -24..+24mA; impedance 40Ω Resistance 0..+400 (1.760) Ω |
OUTPUT CHANNEL | Current 4-20 mA (passive) |
FILTER | Additional for reading stabilization |
SPECIAL FUNCTIONS | Cold junction compensation Insertable filter Output reversal |
A/D CONVERSION | 16 bit |
THERMAL DRIFT | <120 ppm/K |
CONNECTION | 8 spring clamps |
REJECTION | 50 o 60 Hz (programmable) |
PROGRAMMING | EASY SETUP |
INSULATION TECHNIQUE | Digital / Optocoupler |
PROCESSING | 32 bit floating point calculation |
PROTECTION DEGREE | IP20 |
HOUSING | PBT, nero |
DIMENSION (WXHXD) | 6,2x93,1x102,5 mm |
WEIGHT | 45 g |
OPERATING TEMPERATURE | -20..+65°C |
STANDARD | CE |