Trip amplifier 2/209 Pepperl+Fuchs 542492
Trip amplifier 2/209 Pepperl+Fuchs 542492

We are not the manufacturer, authorised distributor or authorised representative of the Pepperl+Fuchs brand in Australia. The private labels and part numbers shown on this website are the property of their respective owners.

Pepperl+Fuchs 2/209 542492

Manufacturer

Pepperl+Fuchs

Country

Germany

Name

2/209

Part number

542492

Type

Trip amplifier

Description

  • 4-channel
  • Input 0/4 mA ... 20 mA
  • 4 relay contact outputs
  • Programmable
  • Simple operation via front buttons
  • Lead monitoring
  • Galvanic isolation between input, power supply and contact output
  • With computational function SIL3
  • LCD display
  • Self-monitoring

Stock availability:

On request

Price: On request

Order

Several positions are needed?

Send your request on email:

Worldwide delivery services:
fedex dhl ups
Ways of payment:
wire transfer paypal

Specifications 2/209 542492

The programmable self-monitoring device is used to line monitor external set points, gradients, ratios or min/max selections. Set points are programmable via front push-buttons or PC. Input, power supply and relay contact output are galvanically isolated.

Features 2/209 542492

Product Description
Trip amplifier with 1-4 trip values
General specifications
Signal typeAnalog input
Supply
Connectionz2+, z4-, z6 (PE)
Rated voltage18 ... 30 V DC 18 ... 26.4 V AC 48 ... 62 Hz
Power consumption2 W / 2.5 VA
Input
ConnectionInput A I: d32+, z32- Input A II: d30+, z30- Input A III: d28+, z28- Input A IV: d26+, z26- Input B I: b32+, z32- Input B II:b30+, z30- Input B III: b28+, z28- Input B IV: b26+, z26-
Input resistance50 &Omega, (mA) 10 k&Omega, (V)
Current range0/4 ... 20 mA (0/1 ... 5 V)
Output
ConnectionOutput I: z10, d12, d10 Output II: d14, z14, z12 Output III: z16, d18, d16 Output IV: d20, z20, z18
Relay
Switching voltage50 V
Switching current2 A AC/DC
Switching power500 VA / 60 W
Mechanical life50 Mio. cycles
Electrical life0.5 Mio. cycles
Response time> 20 ms (variable)
Indicators/settings
Display elementsLED 1: trip value 1 LED 2: trip value 2 LED 3: trip value 3 LED 4: trip value 4 LED green: Power on
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1:2006
Ambient conditions
Ambient temperature-10 ... 60 °C (14 ... 140 °F)
Storage temperature-25 ... 80 °C (-13 ... 176 °F)
Mechanical specifications
Mass300 g
Dimensions22 x 143 x 193 mm (0.9 x 5.6 x 7.6 inch)
Certificates and approvals
SIL classificationSIL3 (IEC 61508) TÜV Rheinland 968/EL 292-03/08