Description

  • Housing with push-in connection technology and mechanically coded terminal blocks
  • Housing width 19 mm, installation in the switch cabinet on DIN mounting rail
  • Sensors can be supplied either from the AS-Interface or external auxiliary voltage, as preferred
  • Function indicator for the bus, external auxiliary voltage, internal sensor supply, and inputs

Stock availability:

On request

253.83 €

Need cheaper?

Several positions are needed?

Send your request on email:

Worldwide delivery services:
fedex dhl ups
Ways of payment:
wire transfer paypal

Specifications VBA-2E-KE5-IJL/UJL 288595

The AS-Interface connecting module VBA-2E-KE5-IJL/UJL is a switch cabinet module with 2 analog outputs for voltage or current. The housing is only 19 mm wide and takes up little space in the switch cabinet. The module is mounted by snapping it onto the 35 mm DIN rail in compliance with EN 50022. The connection is made via removable 4-pin push-in terminal blocks. For AS-i+, AS-i-, AUX+, and AUX-, two connections are available in each case, these connections are bridged in the terminal block. If the terminal block is disconnected from the module, the link between these connections is retained. The terminal blocks are mechanically coded. The supply to the inputs and the connected sensors can be fed either from the internal supply of the module from the AS-Interface or via an external UAUX auxiliary voltage. A switch located on the side of the module changes the source. The relevant IN LED displays the current status of the inputs. If input signals are valid, the corresponding IN LED lights up permanently. If signals are outside the measuring range, the corresponding IN LED flashes. The analog values are transmitted asynchronously with a data width of 16 bits as defined by AS-Interface profile 7.3. The value range of the current input is 0&hellip, 20,000 without wire break detection and 4000&hellip, 20,000 with wire break detection. The value range of the voltage input is 0 &hellip, 10,000. Grid failures can be filtered using a parameterizable filter at 50 Hz or 60 Hz. Notes: Overloading of the internal input supply, absence of the external UAUX voltage source, measuring overrange, and a wire break at the current input are reported as peripheral faults to the AS-Interface master. If the wire break detection is disabled, the extended current measuring range can be used. A jumper between GND and 1CH or the parameter P1 can deactivate input channel 2. The jumper has priority here. If no jumper is set and P1 = 1, then both channels are active. Do not connect the 1CH and GND connections to external potentials. The length of the jumpers must not exceed 5 cm.

Features VBA-2E-KE5-IJL/UJL 288595

Product Description
Switch cabinet module 2 analog Inputs
General specifications
Slave typeStandard slave
AS-Interface specificationV3.0
Required master specification&ge, V2.1
UL File NumberE223772
MTBF154 a
Indicators/operating means
LED FAULTFault indication: red LED Red: communication error or address is 0 Red flashing: peripheral fault
LED INTInternal input supply active, LED green
LED PWRAS-Interface voltage, green LED Green: voltage OK Flashing green: address 0 or peripheral error
LED AUXext. auxiliary voltage UAUX, dual LED green/red green: voltage OK red: reverse voltage
LED INstatus of input signal, LED yellow off: not active on: signal within measurement range flashing: signal outside of measurement range
Electrical specifications
Auxiliary voltage (output)20 ... 30 V DC PELV
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current&le, 70 mA (without sensors) / max. 200 mA
Protection classIII
Current consumptionIAUX &le, 650 mA
Surge protectionUAUX, Ue: overvoltage category II, safe isolated power supplies (PELV)
Input
Number/Type2 analog inputs Current: 0 ... 20 mA/4 ... 20 mA voltage: 0 ... 10 V
SupplyFrom AS-Interface (switch setting INT, default setting) or from auxiliary voltage UAUX (switch setting AUX)
Current loading capacity&le, 100 mA from AS-Interface, overload and short-circuit resistant &le, 600 mA From auxiliary voltage UAUX (AUX switch position) , overload and short-circuit protected
Input resistancecurrent input: max. 70 &Omega, voltage input: 100 k&Omega,
Accuracy0.1 % of input signal range at 25 °C (298 K)
Resolution15 Bit
Temperature influence0.0025 %/K of input signal range
Output
Temperature influence1 µ,A/K or 0,3 mV/K
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013
Standard conformity
Degree of protectionEN 60529:2000
Fieldbus standardEN 62026-2:2013
Emitted interferenceEN 61000-6-4:2007
AS-InterfaceEN 62026-2:2013
Noise immunityEN 61000-6-2:2005, EN 61326-1:2006, EN 62026-2:2013
Programming instructions
ProfileS-7.3.D
IO code7
ID code3
ID1 codeF
ID2 codeD
Data bits (function via AS-Interface)The transfer of the data value is based on AS-Interface Profile 7.3.
Parameter bits (programmable via AS-i)function
P050/60 Hz filter P0=1, enabled P0=0, disabled
P1projecting of the 2nd channel P1=1, channel 2 is projected P1=0, channel 2 is not projected
P2Indication of the peripheral fault by exceeding measuring range P2=1, peripheral fault is reported P2=0, peripheral fault is not reported
P3P3=1, normal operating mode P3=0, both channels in current mode and without recognition of wire breakage
Ambient conditions
Ambient temperature-25 ... 70 °C (-13 ... 158 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity85 % , noncondensing
Climatic conditionsFor indoor use only
Altitude&le, 2000 m above MSL
Shock and impact resistance15 g, 11 ms in 6 spatial directions, 3 shocks 10 g, 16 ms in 6 spatial directions, 1000 shocks
Vibration resistance0.35 mm 10 ... 57 Hz , 5 g 57 ... 150 Hz, 20 cycles
Pollution degree2
Mechanical specifications
Degree of protectionIP20
ConnectionRemovable push-in terminals rated connection capacity: rigid: 0.20 mm2 ... 1.5 mm2 flexible (without wire end ferrule): 0.20 mm2 ... 2.5 mm2 flexible (with wire end ferrule): 0.25 mm2 ... 1.5 mm2
Material
HousingPA 66-FR
Mass110 g
MountingDIN mounting rail
NoteMax. length of jumpers = 5 cm