Inductive sensor NCB15+U4+N0 Pepperl+Fuchs 184673
Inductive sensor NCB15+U4+N0 Pepperl+Fuchs 184673

We are not the manufacturer, authorised distributor or authorised representative of the Pepperl+Fuchs brand in Australia. The private labels and part numbers shown on this website are the property of their respective owners.

Pepperl+Fuchs NCB15+U4+N0 184673

Manufacturer

Pepperl+Fuchs

Country

Germany

Name

NCB15+U4+N0

Part number

184673

Type

Inductive sensor

Description

Inductive sensor NCB15+U4+N0

Stock availability:

On request

Price: On request

Order

Several positions are needed?

Send your request on email:

Worldwide delivery services:
fedex dhl ups
Ways of payment:
wire transfer paypal

Specifications NCB15+U4+N0 184673

If you require NCB15+U4+N0 184673 from manufacturer Pepperl+Fuchs, please contact FAMAGA.

For more than 10 years our specialists supply repair parts for the upgrading and maintenance of various types of manufacturing equipment from all parts of the planet. Over 750 orders from clients from different countries are in progress daily. Developed partner network makes it possible to immediately implement order for Pepperl+Fuchs NCB15+U4+N0, while the client does not have to worry about extra costs.

Geography of deliveries covers Europe, America, Asia and Africa. There is no restrictions on the size and weight of the cargo. We submit for review different delivery options so that a client can choose suitable balance between cost and delivery time.

Company`s main principle of operation is transparency, which includes every sphere of activity. Buyers get top-class spare parts and equipment, to which all necessary certificates are available. All repair parts and equipment are original, risk of presence of counterfeits are excluded. For permanent buyers there are loyalty programs and they are valid great deals.

Become an orderer from FAMAGA, get industrial machinery with no delay and at attractive price. Fill in data in the order form on the website. Our employee will contact you to discuss details. Requests are also accepted by phone.

Features NCB15+U4+N0 184673

General specifications
Switching functionNormally closed (NC)
Output typeNAMUR
Rated operating distance15 mm
Installationflush
Assured operating distance0 ... 12.15 mm
Actual operating distance13.5 ... 16.5 mm typ.
Reduction factor rAl 0.28
Reduction factor rCu 0.25
Reduction factor r304 0.75
Output type2-wire
Nominal ratings
Nominal voltage8.2 V (Ri approx. 1 k&Omega,)
Switching frequency0 ... 400 Hz
Hysteresis1 ... 15 typ. 5 %
Reverse polarity protectionreverse polarity protected
Short-circuit protectionyes
Current consumption
Measuring plate not detectedmin. 3 mA
Measuring plate detected&le, 1 mA
Switching state indicatorLED, yellow
Functional safety related parameters
MTTFd5128 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Compliance with standards and directives
Standard conformity
NAMUREN 60947-5-6:2000 IEC 60947-5-6:1999
Electromagnetic compatibilityNE 21:2007
StandardsEN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012
Approvals and certificates
FM approval
Control drawing116-0165
UL approval
Ordinary LocationE87056
Hazardous LocationE501628
Control drawing116-0451
CSA approvalcCSAus Listed, General Purpose
CCC approvalCCC approval / marking not required for products rated &le,36 V
Ambient conditions
Ambient temperature-25 ... 100 °C (-13 ... 212 °F)
Storage temperature-40 ... 100 °C (-40 ... 212 °F)
Mechanical specifications
Connection typescrew terminals
Information for connectionA maximum of two conductors with the same core cross section may be mounted on one terminal connection! tightening torque 1.2 Nm + 10 %
Core cross-sectionup to 2.5 mm2
Minimum core cross-sectionwithout wire end ferrule 0.5 mm2 , with connector sleeves 0.34 mm2
Maximum core cross-sectionwithout wire end ferrule 2.5 mm2 , with connector sleeves 1.5 mm2
Housing materialPBT/metal
Sensing facePBT
Degree of protectionIP68
NoteTightening torque: 1.8 Nm (housing)
Equipment protection level Ga
CE marking[*PD-Z02585A*]
ATEX marking II 1G Ex ia IIC T6&hellip,T1 Ga The Ex-related marking can also be printed on the enclosed label.
StandardsEN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection Intrinsic safety Use is restricted to the following stated conditions
Appropriate typeNCB15+U...+N0...
Effective internal capacitancemax. 110 nF , a cable length of 10 m is considered.
Effective internal inductancemax. 160 µ,H , a cable length of 10 m is considered.
Ambient temperatureDetails of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate. Note: Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already been applied to the temperature table for category 1.
Equipment protection level Gb
CE marking[*PD-Z02585A*]
ATEX marking II 1G Ex ia IIC T6&hellip,T1 Ga The Ex-related marking can also be printed on the enclosed label.
StandardsEN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection Intrinsic safety Use is restricted to the following stated conditions
Appropriate typeNCB15+U...+N0...
Effective internal capacitancemax. 110 nF , a cable length of 10 m is considered.
Effective internal inductancemax. 160 µ,H , a cable length of 10 m is considered.
Maximum permissible ambient temperatureDetails of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate.
Equipment protection level Da
CE marking[*PD-Z02585A*]
ATEX marking II 1D Ex ia IIIC T135°C Da The Ex-related marking can also be printed on the enclosed label.
StandardsEN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection Intrinsic safety Use is restricted to the following stated conditions
Appropriate typeNCB15+U...+N0...
Effective internal capacitancemax. 110 nF , a cable length of 10 m is considered.
Effective internal inductancemax. 160 µ,H , a cable length of 10 m is considered.
General information
Use in the hazardous areasee instruction manuals
Category1G, 2G, 1D