Fieldbus R-SP-E12 Pepperl+Fuchs 130713
Fieldbus R-SP-E12 Pepperl+Fuchs 130713

We are not the manufacturer, authorised distributor or authorised representative of the Pepperl+Fuchs brand in Australia. The private labels and part numbers shown on this website are the property of their respective owners.

Pepperl+Fuchs R-SP-E12 130713

Manufacturer

Pepperl+Fuchs

Country

Germany

Name

R-SP-E12

Part number

130713

Type

Fieldbus

Description

  • 12 increased safety outputs (Ex e)
  • Short circuit current limitation per output
  • Segment Protector in Zone 1/Div. 2
  • Instruments in Zone 1/Div. 1
  • For FOUNDATION Fieldbus H1 and PROFIBUS PA
  • High power on trunk and spurs

Stock availability:

On request

741.6 €

Need cheaper?

Several positions are needed?

Send your request on email:

Worldwide delivery services:
fedex dhl ups
Ways of payment:
wire transfer paypal

Specifications R-SP-E12 130713

The R SP E12 Segment Protector is a device coupler that connects field instruments to the segment. Flameproof (Ex d) field devices are connected to the trunk line via one output each. Trunk and spurs are certified increased safety (Ex e). Short-circuit protection ensures proper operation of the segment in case of unwanted faults at the spur. Work on devices always requires a hot work permit. The integrated fieldbus terminator features high-availability design and is selectable. Connectors are fixed screw terminals. Any grounding and shielding concept is possible based on FieldConnex enclosure solutions. Customizable housings host one or more Segment Protectors for different output counts.

Features R-SP-E12 130713

Product Description
Segment Protector for Cabinet Installation
General specifications
Design / MountingCabinet installation
Fieldbus interface
Power dissipation250 mW
Main cable (Trunk)
Rated voltage9 ... 32 V DC
Outputs
Number of outputs12
Rated voltagemax. 32 V
Rated currentmax. 40 mA
Short-circuit currentmax. 52 mA
Self current consumptionmax. 9 mA
Voltage drop main cable/outputsmax. 1.3 V
Terminating resistorselectable 100 &Omega, integrated
Surge protectiontrunk, spurs overvoltage protected if voltage exceeds typ. 39 V, max. 41 V
Indicators/operating means
LED PWRgreen: Fieldbus voltage > 10 V
LED CHANNEL ERRORred flashing: short-circuit
LED COMyellow: bus activity
LED TERM ONyellow: termination activated
Directive conformity
Electromagnetic compatibility
Directive 2004/108/ECEN 61326-1:2006
Standard conformity
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529
Fieldbus standardIEC 61158-2
Shock resistanceEN 60068-2-27
Vibration resistanceEN 60068-2-6
Ambient conditions
Ambient temperature-40 ... 70 °C (-40 ... 158 °F)
Storage temperature-40 ... 85 °C (-40 ... 185 °F)
Relative humidity95 % non-condensing
Shock resistance15 g , 11 ms
Vibration resistance5 g , 10 ... 150 Hz
Mechanical specifications
Connection typescrew fixing
Core cross-sectionmax. 2.5 mm2 / AWG 12-24
Housing materialPolycarbonate
Housing width216 mm
Housing height100 mm
Housing depth50 mm
Degree of protectionIP20
Mass800 g
MountingDIN rail mounting
Coatingresin filled
Data for application in connection with hazardous areas
EU-Type Examination CertificatePTB 04 ATEX 2100 X
Marking II 2 G Ex e mb IIC T4 Gb
Maximum values
Rated voltage&le, 35 V
Prospective short-circuit current100 A
Directive conformity
Directive 94/9/ECEN 60079-0:2012 , EN 60079-7:2007 , EN 60079-18:2009
International approvals
IECEx approvalIECEx PTB 05.0010X
Approved forEx me II T4
Certificates and approvals
Marine approvalDNV A-14038