Repeater KFD0-CS-2.50 Pepperl+Fuchs 126992
Repeater KFD0-CS-2.50 Pepperl+Fuchs 126992

We are not the manufacturer, authorised distributor or authorised representative of the Pepperl+Fuchs brand in Australia. The private labels and part numbers shown on this website are the property of their respective owners.

Pepperl+Fuchs KFD0-CS-2.50 126992

Manufacturer

Pepperl+Fuchs

Country

Germany

Name

KFD0-CS-2.50

Part number

126992

Type

Repeater

Description

Repeater KFD0-CS-2.50

Stock availability:

On request

Price: On request

Order

Several positions are needed?

Send your request on email:

Worldwide delivery services:
fedex dhl ups
Ways of payment:
wire transfer paypal

Specifications KFD0-CS-2.50 126992

This signal conditioner provides the galvanic isolation between field circuits and control circuits. The device can be used as a repeater or transmitter power supply for 2-wire transmitters. This device is loop powered. No additional power supply has to be connected. Use the technical data to verify that proper voltage is available to the field devices.

Features KFD0-CS-2.50 126992

Product Description
2-channel
General specifications
Signal typeAnalog input/analog output
Functional safety related parameters
Safety Integrity Level (SIL)SIL 2
Supply
Rated voltageloop powered
Power dissipation0.4 W
Control circuit
Connectionterminals 12-, 11+, 8-, 10-, 9+
Voltage10 ... 35 V DC
Current4 ... 20 mA
Power dissipation< 150 mW per channel at 25 mA and U < 26.1 V 26.1 V
Field circuit
Connectionterminals 1+, 2-, 4+, 5-
Voltage&ge, 0.9 x Uin - (0.23 x current in mA) - 0.7 for 10 V < Uin <26.1 V&ge, 23 V - (0.23 x current in mA) for Uin> 26.1 V
Short-circuit currentmax. 100 mA
Transfer currentmax. 25 mA
Transfer characteristics
Accuracy0.1 %
Rise time&le, 5 ms at 4 ... 20 mA and Uin = input voltage < 26 V
Indicators/settings
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Insulation coordinationEN 50178:1997
Electromagnetic compatibilityNE 21:2006
Degree of protectionIEC 60529:2001
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 100 g
Dimensions20 x 107 x 115 mm (0.8 x 4.2 x 4.5 inch) , housing type B1
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001