Module VBA-2E-G4-I Pepperl+Fuchs 112311
Module VBA-2E-G4-I Pepperl+Fuchs 112311

We are not the manufacturer, authorised distributor or authorised representative of the Pepperl+Fuchs brand in Australia. The private labels and part numbers shown on this website are the property of their respective owners.

Pepperl+Fuchs VBA-2E-G4-I 112311

Manufacturer

Pepperl+Fuchs

Country

Germany

Name

VBA-2E-G4-I

Part number

112311

Type

Module

Description

AS-Interface analog module VBA-2E-G4-I

Stock availability:

On request

532.71 €

Need cheaper?

Several positions are needed?

Send your request on email:

Worldwide delivery services:
fedex dhl ups
Ways of payment:
wire transfer paypal

Specifications VBA-2E-G4-I 112311

The VBA-2E-G4-I analogue module has two analogue current inputs 4 mA ... 20 mA. The asynchronous transformation of measured values and the data transfer is accomplished in accordance with AS-Interface profile 7.3. The measured-value transmitter can be supplied from the AS-Interface or from the external auxiliary power via the black flat cable, depending on the wiring of the plug-in jumpers. The resolution of the analogue values is 16 bit. System disturbances are eliminated, using a programmable filter (50 Hz/60 Hz). The IP65 rated G4 module is especially suitable for rough conditions. Connection to the measured-value transmitters is established by means of cable glands and cage tension spring terminals thus making the installation especially user-friendly. For pre-addressing the module it can be plugged directly onto the adapter of the hand-held programming device VBP-HH1. Both flat and round cables can be used for the connection of the AS-Interface transmission line and the external 24 V DC power supply. Use the U-G1FF base for the AS-Interface flat cable. The AS-Interface standardised EEMS interface, uses the cable piercing method to connect both the yellow and black flat cables. Use the U-G1PP base for a round cable. The AS-Interface cable as well as the external power supply may be connected within the U-G1PP base.

Features VBA-2E-G4-I 112311

Product Description
G4 module IP65 2 analog inputs (current)
General specifications
Slave typeStandard slave
AS-Interface specificationV2.1
Required master specification&ge, V2.1
UL File NumberE223772
Functional safety related parameters
MTTFd160 a at 30 °C
Indicators/operating means
LED FAULTerror display, LED red red: communication error red flashing: peripheral error
LED PWRAS-Interface voltage, LED green
LED ANALOGstatus input signal, LED green off: 1 <1 mA (peripheral error)green: 1 mA &le, I &le, 1 23 mAgreen flashing: I> 23 mA (peripheral error)
LED AUXext. auxiliary voltage UAUX , LED green
Electrical specifications
Auxiliary voltage (output)24 V DC ± 15 % PELV
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current&le, 80 mA
Protection classIII
Input
Number/Type2 analog inputs (currrent), 4 ... 20 mA
Supplyfrom AS-Interface or from external auxiliary voltage as required UAUX
Current loading capacity&le, 200 mA from AS-Interface &le, 500 mA from external auxiliary voltage UAUX
Input resistance50 &Omega,
Resolution16 Bit / 1 µ,A
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013
Standard conformity
Degree of protectionEN 60529:2000
AS-InterfaceEN 62026-2:2013
Programming instructions
ProfileS-7.3.D
IO code7
ID code3
ID2 codeD
Data bits (function via AS-Interface)The transfer of the data value is based on AS-Interface Profile 7.3.
Parameter bits (programmable via AS-i)function
P0mains power frequency filter P0=1, 50 Hz filter active P0=0, 60 Hz filter active
P1projecting of the 2nd channel P1=1, channel 2 is projected P1=0, channel 2 is not projected
P2Message of peripheral error P2=1, peripheral error is reported P2=0, peripheral error is not reported
P3not used
Ambient conditions
Ambient temperature0 ... 70 °C (32 ... 158 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Mechanical specifications
Degree of protectionIP65
Connectioncable piercing method or terminal compartment yellow flat cable/black flat cable or standard round cable inputs/outputs: 2 x M16 x 1.5 cable glands and cage tension spring terminals, 1 x M12 x 1.5 cable gland (not used)
Material
HousingPA 6 GF30
Mass350 g
MountingDIN mounting rail