Inductive sensor NJ40+U4+N Pepperl+Fuchs 106693
Inductive sensor NJ40+U4+N Pepperl+Fuchs 106693

We are not the manufacturer, authorised distributor or authorised representative of the Pepperl+Fuchs brand in Australia. The private labels and part numbers shown on this website are the property of their respective owners.

Pepperl+Fuchs NJ40+U4+N 106693

Manufacturer

Pepperl+Fuchs

Country

Germany

Name

NJ40+U4+N

Part number

106693

Type

Inductive sensor

Description

Inductive sensor NJ40+U4+N

Stock availability:

On request

Price: On request

Order

Several positions are needed?

Send your request on email:

Worldwide delivery services:
fedex dhl ups
Ways of payment:
wire transfer paypal

Specifications NJ40+U4+N 106693

If you require NJ40+U4+N 106693 from manufacturer Pepperl+Fuchs, please contact FAMAGA.

For more than 9 years our employees supply repair parts for the upgrade and maintenance of various types of industrial equipment from all corners of the earth. Over 750 orders from clients from countries of near and far abroad are in service daily. Developed partner network allows you to quickly execute order for Pepperl+Fuchs NJ40+U4+N, while the client does not have to spend more than planned amount.

Geography of deliveries involves Europe, America, Asia and Africa. There is no restrictions on the size and mass of the cargo. We developed different delivery options so that a client can choose optimal compromise between cost and delivery time.

Company`s fundamental rule of operation is transparency, which covers every segment of activity. Customers get top-class spare parts and equipment, to which relevant documentation from the manufacturer is available. All repair parts and equipment are original, risk of presence of counterfeits are excluded. For permanent customers there are exclusive offers and they are valid great deals.

Become an orderer from FAMAGA, get goods with no delays and at beneficial price. Fill in information in the order form on the website. Manager will contact you to discuss nuances. Inquiries are also accepted by phone.

Features NJ40+U4+N 106693

General specifications
Switching functionNormally closed (NC)
Output typeNAMUR
Rated operating distance40 mm
Installationnon-flush
Assured operating distance0 ... 32.4 mm
Reduction factor rAl 0.4
Reduction factor rCu 0.3
Reduction factor r304 0.85
Output type2-wire
Nominal ratings
Nominal voltage8.2 V (Ri approx. 1 k&Omega,)
Switching frequency0 ... 80 Hz
Current consumption
Measuring plate not detected&ge, 3 mA
Measuring plate detected&le, 1 mA
Functional safety related parameters
MTTFd2588 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Compliance with standards and directives
Standard conformity
NAMUREN 60947-5-6:2000 IEC 60947-5-6:1999
StandardsEN 60947-5-2:2007 IEC 60947-5-2:2007
Approvals and certificates
FM approval
Control drawing116-0165
UL approvalcULus Listed, General Purpose
CSA approvalcCSAus Listed, General Purpose
CCC approvalCCC approval / marking not required for products rated &le,36 V
Ambient conditions
Ambient temperature-25 ... 100 °C (-13 ... 212 °F)
Mechanical specifications
Connection typescrew terminals
Information for connectionA maximum of two conductors with the same core cross section may be mounted on one terminal connection! tightening torque 1.2 Nm + 10 %
Core cross-sectionup to 2.5 mm2
Minimum core cross-sectionwithout wire end ferrule 0.5 mm2 , with connector sleeves 0.34 mm2
Maximum core cross-sectionwithout wire end ferrule 2.5 mm2 , with connector sleeves 1.5 mm2
Housing materialPBT/metal
Sensing facePBT
Degree of protectionIP68
Equipment protection level Gb
CE marking[*PD-Z02585A*]
ATEX marking II 2G Ex ia IIC T6&hellip,T1 Gb The Ex-related marking can also be printed on the enclosed label.
StandardsEN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection Intrinsic safety Use is restricted to the following stated conditions
Appropriate typeNJ 40+...+N...
Effective internal capacitancemax. 180 nF , a cable length of 10 m is considered.
Effective internal inductancemax. 130 µ,H , a cable length of 10 m is considered.
Maximum permissible ambient temperatureDetails of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EU-type examination certificate.
Equipment protection level Da
CE marking[*PD-Z02585A*]
ATEX marking II 1D Ex ia IIIC T135°C Da The Ex-related marking can also be printed on the enclosed label.
StandardsEN 60079-0:2012+A11:2013, EN 60079-11:2012 Ignition protection Intrinsic safety Use is restricted to the following stated conditions
Appropriate typeNJ 40+...+N...
Effective internal capacitancemax. 180 µ,F A cable length of 10 m is considered.
Effective internal inductancemax. 130 µ,H A cable length of 10 m is considered.
General information
Use in the hazardous areasee instruction manuals
Category2G