Inductive sensor NJ0,8-5GM-N Pepperl+Fuchs 106334
Inductive sensor NJ0,8-5GM-N Pepperl+Fuchs 106334

We are not the manufacturer, authorised distributor or authorised representative of the Pepperl+Fuchs brand in Australia. The private labels and part numbers shown on this website are the property of their respective owners.

Pepperl+Fuchs NJ0,8-5GM-N 106334

Manufacturer

Pepperl+Fuchs

Country

Germany

Name

NJ0,8-5GM-N

Part number

106334

Type

Inductive sensor

Description

Inductive sensor NJ0,8-5GM-N

Stock availability:

On request

Price: On request

Order

Several positions are needed?

Send your request on email:

Worldwide delivery services:
fedex dhl ups
Ways of payment:
wire transfer paypal

Specifications NJ0,8-5GM-N 106334

If you require NJ0,8-5GM-N 106334 from manufacturer Pepperl+Fuchs, please contact FAMAGA.

For more than 9 years our specialists supply repair parts for the repair and maintenance of various types of industrial equipment from all over the world. Over 600 orders from clients from countries of near and far abroad are in service daily. Developed partner network allows you to quickly execute order for Pepperl+Fuchs NJ0,8-5GM-N, while the customer does not have to spend more than planned amount.

Geography of deliveries involves Europe, America, Asia and Africa. There is no restrictions on the size and mass of the cargo. We offer different delivery options so that a client can choose suitable balance between cost and delivery time.

Company`s fundamental rule of operation is transparency, which covers every sphere of activity. Customers get top-class spare parts and equipment, to which relevant documentation from the manufacturer is available. All repair parts and equipment are original, likelihood of counterfeits are excluded. For permanent customers there are very good terms and they are valid great deals.

Become an orderer from FAMAGA, get industrial machinery with no delays and at beneficial price. Fill in information in the order form on the website. Manager will contact you to specify details. Inquiries are also accepted by phone.

Features NJ0,8-5GM-N 106334

General specifications
Switching functionNormally closed (NC)
Output typeNAMUR
Rated operating distance0.8 mm
Installationflush
Assured operating distance0 ... 0.65 mm
Reduction factor rAl 0.4
Reduction factor rCu 0.3
Reduction factor r304 0.85
Output type2-wire
Nominal ratings
Nominal voltage8.2 V (Ri approx. 1 k&Omega,)
Operating voltage5 ... 25 V
Switching frequency0 ... 5000 Hz
Hysteresis3 %
Suitable for 2:1 technologyyes , Reverse polarity protection diode not required
Current consumption
Measuring plate not detected&ge, 3 mA at nominal voltage
Measuring plate detected&le, 1 mA at nominal voltage
Functional safety related parameters
MTTFd1050 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Compliance with standards and directives
Standard conformity
NAMUREN 60947-5-6:2000 IEC 60947-5-6:1999
StandardsEN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012
Approvals and certificates
EAC conformityTR CU 012/2011
FM approval
Control drawing116-0165
UL approval
Ordinary LocationE87056
Hazardous LocationE501628
Control drawing116-0452
CSA approvalcCSAus Listed, General Purpose
CCC approvalCCC approval / marking not required for products rated &le,36 V
Ambient conditions
Ambient temperature-25 ... 100 °C (-13 ... 212 °F)
Mechanical specifications
Connection typecable PVC , 2 m
Core cross-section0.14 mm2
Housing materialStainless steel 1.4305 / AISI 303
Sensing facePBT
Degree of protectionIP67
Cable
Cable diameter2.6 mm ± 0.2 mm
Bending radius> 10 x cable diameter
Equipment protection level Ga
CE marking[*PD-Z02585A*]
ATEX marking II 1G Ex ia IIC T6&hellip,T1 Ga The Ex-related marking can also be printed on the enclosed label.
StandardsEN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection Intrinsic safety Use is restricted to the following stated conditions
Appropriate typeNJ 0,8-5GM-N...
Effective internal capacitancemax. 30 nF , a cable length of 10 m is considered.
Effective internal inductancemax. 50 µ,H , a cable length of 10 m is considered.
Ambient temperatureDetails of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate. Note: Use the temperature table for category 1 !!! The 20 % reduction in accordance with EN 1127-1 has already been applied to the temperature table for category 1.
Equipment protection level Gb
CE marking[*PD-Z02585A*]
ATEX marking II 1G Ex ia IIC T6&hellip,T1 Ga The Ex-related marking can also be printed on the enclosed label.
StandardsEN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection Intrinsic safety Use is restricted to the following stated conditions
Appropriate typeNJ 0,8-5GM-N...
Effective internal capacitancemax. 30 nF , a cable length of 10 m is considered.
Effective internal inductancemax. 50 µ,H , a cable length of 10 m is considered.
Maximum permissible ambient temperatureDetails of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate.
Equipment protection level Da
CE marking[*PD-Z02585A*]
ATEX marking II 1D Ex ia IIIC T135°C Da The Ex-related marking can also be printed on the enclosed label.
StandardsEN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection Intrinsic safety Use is restricted to the following stated conditions
Appropriate typeNJ0,8-5GM-N...
Effective internal capacitancemax. 30 nF , a cable length of 10 m is considered.
Effective internal inductancemax. 50 µ,H , a cable length of 10 m is considered.
Maximum permissible ambient temperature Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the surface temperature, and the effective internal reactance values can be found on the EC-type-examination certificate. The maximum permissible ambient temperature of the data sheet must be noted, in addition, the lower of the two values must be maintained.
General information
Use in the hazardous areasee instruction manuals
Category1G, 2G, 1D