Specifications NJ1,5-18GM-N-D 106342

If you require NJ1,5-18GM-N-D 106342 from manufacturer Pepperl+Fuchs, please contact FAMAGA.

For more than 10 years our employees supply spare parts for the upgrade and maintenance of various types of technical equipment from all corners of the earth. Over 750 orders from clients from different countries are arrived daily. Developed partner network makes it possible to immediately implement order for Pepperl+Fuchs NJ1,5-18GM-N-D, while the client does not have to worry about extra costs.

Geography of deliveries covers Europe, Asia, America and Africa. There is no restrictions on the size and mass of the cargo. We developed different delivery options so that a buyer can choose suitable balance between cost and delivery time.

Company`s main principle of operation is transparency, which includes every segment of activity. Buyers get only high-quality products, to which factory warranty applies. All repair parts and equipment are original, likelihood of counterfeits are excluded. For permanent partners there are very good terms and they are valid special pricing.

Become an orderer from FAMAGA, get machine-tools with no delay and at attractive price. Fill in the order form on the website. Our specialist will contact you to discuss nuances. Orders are also accepted by phone.

Features NJ1,5-18GM-N-D 106342

General specifications
Switching functionNormally closed (NC)
Output typeNAMUR
Rated operating distance1.5 mm
Installationflush
Assured operating distance0 ... 1.22 mm
Reduction factor rAl 0
Reduction factor rCu 0
Reduction factor r304 0.55
Output type2-wire
Nominal ratings
Nominal voltage8.2 V (Ri approx. 1 k&Omega,)
Switching frequency0 ... 400 Hz
Hysteresistyp. %
Current consumption
Measuring plate not detectedmin. 3 mA
Measuring plate detected&le, 1 mA
Limit data
Operating pressure350 bar (5076.4 psi)
Functional safety related parameters
MTTFd10880 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Compliance with standards and directives
Standard conformity
NAMUREN 60947-5-6:2000 IEC 60947-5-6:1999
StandardsEN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012
Approvals and certificates
EAC conformityTR CU 012/2011
UL approvalcULus Listed, General Purpose
CSA approvalcCSAus Listed, General Purpose
Ambient conditions
Ambient temperature-25 ... 85 °C (-13 ... 185 °F)
Mechanical specifications
Connection typecable PVC , 2 m
Core cross-section0.34 mm2
Housing materialStainless steel 1.4305 / AISI 303
Sensing faceCeramic
Degree of protectionIP66 / IP68
Cable
Cable diameter4.8 mm ± 0.2 mm
Bending radius> 10 x cable diameter
Equipment protection level Gb
CE marking[*PD-Z02585A*]
ATEX marking II 2G Ex ia IIC T6&hellip,T1 Gb The Ex-related marking can also be printed on the enclosed label.
StandardsEN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection Intrinsic safety Use is restricted to the following stated conditions
Appropriate typeNJ1,5-18GM-N-D..
Effective internal capacitancemax. 50 nF , a cable length of 10 m is considered.
Effective internal inductancemax. 60 µ,H , a cable length of 10 m is considered.
Maximum permissible ambient temperatureDetails of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the temperature class, and the effective internal reactance values can be found on the EC-type examination certificate.
Equipment protection level Da
CE marking[*PD-Z02585A*]
ATEX marking II 1D Ex ia IIIC T135°C Da The Ex-related marking can also be printed on the enclosed label.
StandardsEN 60079-0:2012+A11:2013 EN 60079-11:2012 Ignition protection Intrinsic safety Use is restricted to the following stated conditions
Appropriate typeNJ1,5-18GM-N-D..
Effective internal capacitancemax. 50 nF , a cable length of 10 m is considered.
Effective internal inductancemax. 60 µ,H , a cable length of 10 m is considered.
Maximum permissible ambient temperature Details of the correlation between the type of circuit connected, the maximum permissible ambient temperature, the surface temperature, and the effective internal reactance values can be found on the EC-type-examination certificate. The maximum permissible ambient temperature of the data sheet must be noted, in addition, the lower of the two values must be maintained.
General information
Use in the hazardous areasee instruction manuals
Category2G, 1D