Module VBA-2E2A-G4-ZE/E2 Pepperl+Fuchs 088914
Module VBA-2E2A-G4-ZE/E2 Pepperl+Fuchs 088914

We are not the manufacturer, authorised distributor or authorised representative of the Pepperl+Fuchs brand in Australia. The private labels and part numbers shown on this website are the property of their respective owners.

Pepperl+Fuchs VBA-2E2A-G4-ZE/E2 088914

Manufacturer

Pepperl+Fuchs

Country

Germany

Name

VBA-2E2A-G4-ZE/E2

Part number

088914

Type

Module

Description

AS-Interface sensor/actuator module VBA-2E2A-G4-ZE/E2

Stock availability:

On request

Price: On request

Order

Several positions are needed?

Send your request on email:

Worldwide delivery services:
fedex dhl ups
Ways of payment:
wire transfer paypal

Specifications VBA-2E2A-G4-ZE/E2 088914

The VBA-2E2A-G4-ZE/E2 AS-Interface module is equipped with 2 inputs and 2 outputs. The inputs permit the connection of mechanical contacts and of 2- and 3-wire sensors, The sensors are supplied via the module. The outputs are electronic outputs, which can be loaded to 24 V DC and 1 A per output. The IP67 rated G4 module is particularly suitable for rough conditions. Sensors and actuators attach to cable glands and cage tension spring terminals thus making the installation especially user-friendly. For pre-addressing the module it can be plugged directly onto the adapter of the hand-held programming device VBP-HH1. The current switching state of each channel is indicated by an LED, located on the module's top side. In the case of communication errors on the bus, the outputs are de-energised via an integrated watchdog. Both flat and round cables can be used for the connection of the AS-Interface transmission line and the external 24 V DC power supply. Use the U-G1FF base for the AS-Interface flat cable. The AS-Interface standardised EEMS interface, uses the cable piercing method to connect both the yellow and black flat cables. Use the U-G1PP base for a round cable. The AS-Interface-cable as well as the external power supply may be connected within the U-G1PP base. Note: The device incorporates communication monitoring, which switches off power to the outputs if no communication has taken place on the AS-Interface line for longer than 40 ms. An overloading of the internal input supply or of the outputs is signalled to the AS-Interface master via the Peripheral fault function. Communication via the AS-Interface remains intact.

Features VBA-2E2A-G4-ZE/E2 088914

Product Description
G4 module IP67 2 inputs (PNP) and 2 electronic outputs
General specifications
Slave typeA/B slave
AS-Interface specificationV2.1
Required master specification&ge, V2.1
UL File NumberE223772
Indicators/operating means
LED PWR/FAULTdual LED green/red green: AS-Interface voltage red: communication error or address 0 green/red flashing: overload sensor supply or outputs
LED INswitching state (input), 2 LED yellow
LED OUTSwitching state (output), 2 LED yellow
Electrical specifications
Auxiliary voltage (output)24 V DC ± 15 % PELV
Rated operating voltage26.5 ... 31.6 V from AS-Interface
Rated operating current&le, 30 mA (without sensors) / max. 140 mA
Protection classIII
Surge protectionUAUX, Uin: Over voltage category III, safe isolated power supplies (PELV)
Input
Number/Type2 inputs for 2- or 3-wire sensors (PNP), DC
Supplyfrom AS-Interface
Voltage21 ... 31 V
Current loading capacity&le, 100 mA (TB &le, 40 °C), &le, 75 mA (TB &le, 60 °C), overload-proof and short-circuit protected
Input current&le, 8 mA (limited internally)
Switching pointaccording to DIN EN 61131-2 (Type 2)
0 (unattenuated)&le, 2 mA
1 (attenuated)&ge, 4 mA
Output
Number/Type2 electronic outputs, PNP overload and short-circuit proof
Supplyfrom external auxiliary voltage UAUX
Current1 A per output
Voltage&ge, (UAUX - 0.5 V)
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 62026-2:2013 EN 61000-6-2:2001 EN 61000-6-4:2001
Standard conformity
Degree of protectionEN 60529:2000
InputEN 61131-2:2007
Emitted interferenceEN 61000-6-4:2001
AS-InterfaceEN 62026-2:2013
Noise immunityEN 61000-6-2:2001
Programming instructions
ProfileS-B.A.0
IO codeB
ID codeA
ID1 code7
ID2 code0
Data bits (function via AS-Interface) input output
D0 - OUT1
D1 - OUT2
D2 IN3 -
D3 IN4 -
Parameter bits (programmable via AS-i)function
P0not used
P1not used
P2not used
P3not used
Ambient conditions
Ambient temperature-25 ... 60 °C (-13 ... 140 °F)
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Relative humidity85 % , noncondensing
Climatic conditionsFor indoor use only
Altitude&le, 2000 m above MSL
Pollution degree3
Mechanical specifications
Degree of protectionIP67
Connectioncable piercing method or terminal compartment yellow flat cable/black flat cable or standard round cable inputs/outputs:M12 x 1.5 cable glands and cage tension spring terminals
Material
HousingPA 6 GF30
Mass180 g
Tightening torque, housing screws0.8 Nm
MountingDIN rail or screw mounting