Signal Converter KFD0-TR-Ex1 Pepperl+Fuchs 043691
Signal Converter KFD0-TR-Ex1 Pepperl+Fuchs 043691

We are not the manufacturer, authorised distributor or authorised representative of the Pepperl+Fuchs brand in Australia. The private labels and part numbers shown on this website are the property of their respective owners.

Pepperl+Fuchs KFD0-TR-Ex1 043691

Manufacturer

Pepperl+Fuchs

Country

Germany

Name

KFD0-TR-Ex1

Part number

043691

Type

Signal Converter

Description

RTD Converter KFD0-TR-Ex1

Stock availability:

On request

Price: On request

Order

Several positions are needed?

Send your request on email:

Worldwide delivery services:
fedex dhl ups
Ways of payment:
wire transfer paypal

Specifications KFD0-TR-Ex1 043691

This isolated barrier is used for intrinsic safety applications. It is a loop-powered isolator that converts the resistance from a 3-wire RTD in the hazardous area to a 4 mA ... 20mA signal in the safe area. A selectable analog linearization ensures a temperature linear 4 mA ... 20mA output between 25 °C ... 375 °C. It also features conveniently located DIP switches, rotary switches and potentiometers to make field calibration easy.

Features KFD0-TR-Ex1 043691

General specifications
Signal typeAnalog input
Supply
Rated voltage12 ... 35 V DC loop powered
Power dissipation0.4 W
Input
Connection sidefield side
Connectionterminals 1, 2-, 3+ suitable for Pt100, 2- and 3-wire connection
Lead resistancemax. 100 &Omega, per line
Measuring currentapprox. 1 mA
Output
Connection sidecontrol side
Connectionterminals 9+, 8-
Load(U -12 V) / 0.02 A
Current output4 ... 20 mA , limited to &le, 35 mA
Fault signalupscaling &ge, 22 mA (limited to 35 mA)
Transfer characteristics
Measurement rangespan without linearization 25 ... 800 °C (77 ... 1472 °F)/with linearization 25 ... 375 °C (77 ... 707 °F), both adjustable zero point without linearization -200 ... 400 °C (-328 ... 752 °F)/with linearization -30 ... 375 °C (-22 ... 707 °F), both adjustable
Deviation
After calibration0.1 % of full-scale value incl. linearity and hysteresis
Influence of ambient temperaturespan and zero point 0.015 % / K or ± 10 m&Omega, / K
Influence of supply voltage6.5 ppm/V
Rise time250 ms
Galvanic isolation
Input/Outputavailable
Indicators/settings
Control elementsDIP-switch rotary switch
Configurationvia DIP switches via rotary switch
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Insulation coordinationEN 50178
Galvanic isolationEN 50178
Degree of protectionIEC 60529
Ambient conditions
Ambient temperature-20 ... 60 °C (-4 ... 140 °F)
Mechanical specifications
Degree of protectionIP20
Connectionscrew terminals
Massapprox. 150 g
Dimensions20 x 119 x 115 mm (0.8 x 4.7 x 4.5 inch) , housing type B2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-Type Examination CertificateZELM 00 ATEX 0036
Marking II (1)GD [EEx ia] IIC
Voltage16.1 V
Current33 mA
Power131 mW
CertificateTÜV 01 ATEX 1777 X
Marking II 3G Ex nA II T4
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
CSA approval
Control drawing116-0132
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.