Solenoid Driver KCD0-SD3-Ex1.1245.SP Pepperl+Fuchs 315050
Solenoid Driver KCD0-SD3-Ex1.1245.SP Pepperl+Fuchs 315050

We are not the manufacturer, authorised distributor or authorised representative of the Pepperl+Fuchs brand in Australia. The private labels and part numbers shown on this website are the property of their respective owners.

Pepperl+Fuchs KCD0-SD3-Ex1.1245.SP 315050

Manufacturer

Pepperl+Fuchs

Country

Germany

Name

KCD0-SD3-Ex1.1245.SP

Part number

315050

Type

Solenoid Driver

Description

  • 1-channel isolated barrier
  • 24 V DC supply (loop powered)
  • Current limit 45 mA at 12 V DC
  • Test pulse immunity
  • Housing width 12.5 mm
  • Connection via spring terminals with push-in connection technology
  • Up to SIL 3 acc. to IEC 61508

Stock availability:

On request

Price: On request

Order

Several positions are needed?

Send your request on email:

Worldwide delivery services:
fedex dhl ups
Ways of payment:
wire transfer paypal

Specifications KCD0-SD3-Ex1.1245.SP 315050

This isolated barrier is used for intrinsic safety applications. The device supplies power to solenoids, LEDs and audible alarms located in a hazardous area. The device is loop powered, so the available energy at the output is received from the input signal. The output signal has a resistive characteristic. As a result the output voltage and current are dependent on the load and the input voltage At full load, 12 V at 45 mA is available for the hazardous area application.

Features KCD0-SD3-Ex1.1245.SP 315050

Product Description
current limit 45 mA
General specifications
Signal typeDigital Output
Functional safety related parameters
Safety Integrity Level (SIL)SIL 3
Supply
Connectionloop powered
Rated voltage19 ... 30 V DC loop powered
Power dissipation< 1.3 W
Input
Connection sidecontrol side
Connectionterminals 5+, 6-
Test pulse lengthmax. 2 ms from DO card
Signal level1-signal: 19 ... 30 V DC 0-signal: 0 ... 5 V DC
Rated voltage19 ... 30 V DC
Rated current0-signal: typ. 1.6 mA at 1.5 V DC, typ. 8 mA at 3 V DC (maximum leakage current DO card) 1-signal: &ge, 36 mA (minimum load current DO card)
Inrush current&le, 200 mA after 100 µ,s
Output
Connection sidefield side
Connectionterminals 1+, 2-
Internal resistorapprox. 240 &Omega,
Currenttyp. 45 mA
Voltage&ge, 12 V
Current limit45 mA
Open loop voltagetyp. 24.6 V
Switching frequencymax. 10 Hz
Energized/De-energized delay28 ms / 10 ms
Galvanic isolation
Output/other circuitsbasic insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff
Indicators/settings
Display elementsLED
Labelingspace for labeling at the front
Directive conformity
Electromagnetic compatibility
Directive 2014/30/EUEN 61326-1:2013 (industrial locations)
Conformity
Electromagnetic compatibilityNE 21:2012 , EN 61326-3-2:2008 For further information see system description.
Degree of protectionIEC 60529:2013
Protection against electrical shockEN 61010-1:2010
Ambient conditions
Ambient temperature-20 ... 70 °C (-4 ... 158 °F)
Mechanical specifications
Degree of protectionIP20
Connectionspring terminals
Massapprox. 150 g
Dimensions12.5 x 114 x 119 mm (0.5 x 4.5 x 4.7 inch) , housing type A2
Mountingon 35 mm DIN mounting rail acc. to EN 60715:2001
Data for application in connection with hazardous areas
EU-type examination certificateEXA 17 ATEX 0002 X
Marking II 3(1)G Ex ec [ia Ga] IIC T4 Gc II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I
OutputEx ia
Voltage26 V
Current110 mA
Power715 mW
Input
Maximum safe voltage60 V (Attention! The rated voltage can be lower.)
Galvanic isolation
Input/Outputsafe electrical isolation acc. to IEC/EN 60079-11, rated insulation voltage 300 Vrms
Directive conformity
Directive 2014/34/EUEN 60079-0:2012+A11:2013 , EN 60079-7:2015 , EN 60079-11:2012 , EN 60079-15:2010
International approvals
UL approvalE106378
Control drawing116-0448 (cULus)
IECEx approval
IECEx certificateIECEx EXA 17.0001X
IECEx markingEx ec [ia Ga] IIC T4 Gc [Ex ia Da] IIIC [Ex ia Ma] I
General information
Supplementary informationObserve the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see www.pepperl-fuchs.com.