Specifications PL3-F25-N4-S 291800

If you require PL3-F25-N4-S 291800 from manufacturer Pepperl+Fuchs, please contact FAMAGA.

For more than 10 years our employees supply repair parts for the renovation and maintenance of various types of manufacturing equipment from all parts of the planet. Over 700 orders from clients from countries of near and far abroad are in progress daily. Developed partner network makes it possible to immediately implement order for Pepperl+Fuchs PL3-F25-N4-S, while the customer does not have to spend more than planned amount.

Geography of deliveries involves Europe, Asia, America and Africa. There is no restrictions on the size and mass of the cargo. We developed different delivery options so that a client can choose suitable balance between cost and delivery time.

Company`s main principle of operation is transparency, which involves every segment of activity. Buyers get only high-quality products, to which relevant documentation from the manufacturer is available. All spare parts and equipment are original, risk of presence of counterfeits are excluded. For permanent customers there are exclusive offers and they are valid great deals.

Become an orderer from FAMAGA, get gear with no delays and at beneficial price. Fill in data in the order form on the website. Manager will contact you to discuss nuances. Inquiries are also accepted by phone.

Features PL3-F25-N4-S 291800

General specifications
Switching function2 x normally closed (NC)
Output typeNAMUR
Rated operating distance3 mm
Installationflush mountable
Assured operating distance0 ... 2.43 mm
Actual operating distance2.6 ... 2.6 mm typ.
Reduction factor rAl 0.52
Reduction factor rCu 0.43
Reduction factor r304 0.86
Reduction factor rSt37 1
Reduction factor rBrass 0.54
Output type2-wire
Nominal ratings
Nominal voltage8.2 V (Ri approx. 1 k&Omega,)
Operating voltage5 ... 25 V
Switching frequency0 ... 100 Hz
Hysteresistyp. 5 %
Reverse polarity protectionreverse polarity protected
Short-circuit protectionyes
Suitable for 2:1 technologyyes , Reverse polarity protection diode not required
Current consumption
Measuring plate not detected&ge, 3 mA at nominal voltage
Measuring plate detected&le, 1 mA at nominal voltage
Time delay before availability&le, 1 ms
Switching state indicatorLED, yellow
Valve status indicatorLED, yellow can be switched off by of DB1
Functional safety related parameters
MTTFd834 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Compliance with standards and directives
Standard conformity
NAMUREN 60947-5-6:2000 IEC 60947-5-6:1999
Electromagnetic compatibilityNE 21:2007
StandardsEN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012
Ambient conditions
Ambient temperature-25 ... 100 °C (-13 ... 212 °F)
Storage temperature-40 ... 100 °C (-40 ... 212 °F)
Mechanical specifications
Connection (system side)screw terminals
Core cross-section (system side)up to 2.5 mm2
Connection (valve side)screw terminals
Core cross-section (valve side)up to 2.5 mm2
Housing materialPBT
Sensing facePBT
Mass91 g
Tightening torque, fastening screws0.3 Nm
NoteInstallation in housing
Data for application in connection with hazardous areas
Equipment protection levelGa , Gb , Gc (ic) , Mb
Equipment protection level Ga
Type of protectionintrinsic safety
CE marking[*PD-Z02585A*]
Certificates
Appropriate typePL...-F25...-N4...
ATEX certificateTÜV 99 ATEX 1479 X
ATEX marking II 1G Ex ia IIC T6...T1 Ga
StandardsEN 60079-0:2012+A11:2013 , EN 60079-11:2012
IECEx certificateIECEx TUN 17.0021X
IECEx markingEx ia IIC T6...T1 Ga
StandardsIEC 60079-0:2011 , IEC 60079-11:2011
Effective internal capacitancemax. 100 nF The value is applicable for one sensor circuit. A cable length of 10 m is considered.
Effective internal inductancemax. 100 µ,H The value is applicable for one sensor circuit. A cable length of 10 m is considered.
Maximum permissible ambient temperatureAlso observe the maximum permissible ambient temperature stated in the general technical data. Keep to the lower of the two values.
for ATEXat Ui = 15 V , Ii = 25 mA , Pi = 34 mW , T6 : 45 °C (113 °F) T5 : 55 °C (131 °F) T4 : 85 °C (185 °F) T3 : 85 °C (185 °F) T2 : 85 °C (185 °F) T1 : 85 °C (185 °F) at Ui = 15 V , Ii = 25 mA , Pi = 64 mW , T6 : 45 °C (113 °F) T5 : 55 °C (131 °F) T4 : 85 °C (185 °F) T3 : 85 °C (185 °F) T2 : 85 °C (185 °F) T1 : 85 °C (185 °F) at Ui = 15 V , Ii = 52 mA , Pi = 169 mW , T6 : 45 °C (113 °F) T5 : 55 °C (131 °F) T4 : 85 °C (185 °F) T3 : 85 °C (185 °F) T2 : 85 °C (185 °F) T1 : 85 °C (185 °F)
for IECExat Ui = 15 V , Ii = 25 mA , Pi = 34 mW , T6 : 60 °C (140 °F) T5 : 75 °C (167 °F) T4 : 100 °C (212 °F) T3 : 100 °C (212 °F) T2 : 100 °C (212 °F) T1 : 100 °C (212 °F) at Ui = 15 V , Ii = 25 mA , Pi = 64 mW , T6 : 60 °C (140 °F) T5 : 75 °C (167 °F) T4 : 100 °C (212 °F) T3 : 100 °C (212 °F) T2 : 100 °C (212 °F) T1 : 100 °C (212 °F) at Ui = 15 V , Ii = 52 mA , Pi = 169 mW , T6 : 60 °C (140 °F) T5 : 75 °C (167 °F) T4 : 95 °C (203 °F) T3 : 95 °C (203 °F) T2 : 95 °C (203 °F) T1 : 95 °C (203 °F)
Maximum values of the valve circuitThe value applies to each valve circuit. A cable length of 10 m is considered.
Voltagemax. 32 V
Currentmax. 240 mA
Internal capacitancemax. 10 nF
Internal inductancemax. 20 µ,H
Equipment protection level Gb
Type of protectionintrinsic safety
CE marking[*PD-Z02585A*]
Certificates
Appropriate typePL...-F25...-N4...
ATEX certificateTÜV 99 ATEX 1479 X
ATEX marking II 1G Ex ia IIC T6&hellip,T1 Ga
StandardsEN 60079-0:2012+A11:2013 , EN 60079-11:2012
IECEx certificateIECEx TUN 17.0021X
IECEx markingEx ia IIC T6...T1 Ga
StandardsIEC 60079-0:2011 , IEC 60079-11:2011
Effective internal capacitancemax. 100 nF The value is applicable for one sensor circuit. A cable length of 10 m is considered.
Effective internal inductancemax. 100 µ,H The value is applicable for one sensor circuit. A cable length of 10 m is considered.
Maximum permissible ambient temperatureAlso observe the maximum permissible ambient temperature stated in the general technical data. Keep to the lower of the two values. at Ui = 15 V , Ii = 25 mA , Pi = 34 mW , T6 : 60 °C (140 °F) T5 : 75 °C (167 °F) T4 : 100 °C (212 °F) T3 : 100 °C (212 °F) T2 : 100 °C (212 °F) T1 : 100 °C (212 °F) at Ui = 15 V , Ii = 25 mA , Pi = 64 mW , T6 : 60 °C (140 °F) T5 : 75 °C (167 °F) T4 : 100 °C (212 °F) T3 : 100 °C (212 °F) T2 : 100 °C (212 °F) T1 : 100 °C (212 °F) at Ui = 15 V , Ii = 52 mA , Pi = 169 mW , T6 : 60 °C (140 °F) T5 : 75 °C (167 °F) T4 : 95 °C (203 °F) T3 : 95 °C (203 °F) T2 : 95 °C (203 °F) T1 : 95 °C (203 °F)
Maximum values of the valve circuitThe value applies to each valve circuit. A cable length of 10 m is considered.
Voltagemax. 32 V
Currentmax. 240 mA
Internal capacitancemax. 10 nF
Internal inductancemax. 20 µ,H
Equipment protection level Gc (ic)
Type of protectionintrinsic safety
CE marking[*PD-Z02585A*]
Certificates
ATEX certificatePF 13 CERT 2895 X
ATEX marking II 3G Ex ic IIC T6&hellip,T1 Gc
StandardsEN 60079-0:2012+A11:2013 , EN 60079-11:2012
Effective internal capacitancemax. 100 nF The value is applicable for one sensor circuit. A cable length of 10 m is considered.
Effective internal inductancemax. 100 µ,H The value is applicable for one sensor circuit. A cable length of 10 m is considered.
Maximum permissible ambient temperatureAlso observe the maximum permissible ambient temperature stated in the general technical data. Keep to the lower of the two values. at Ui = 20 V , Ii = 25 mA , Pi = 34 mW , T6 : 60 °C (140 °F) T5 : 75 °C (167 °F) T4 : 100 °C (212 °F) T3 : 100 °C (212 °F) T2 : 100 °C (212 °F) T1 : 100 °C (212 °F) at Ui = 20 V , Ii = 25 mA , Pi = 64 mW , T6 : 60 °C (140 °F) T5 : 75 °C (167 °F) T4 : 100 °C (212 °F) T3 : 100 °C (212 °F) T2 : 100 °C (212 °F) T1 : 100 °C (212 °F) at Ui = 20 V , Ii = 52 mA , Pi = 169 mW , T6 : 60 °C (140 °F) T5 : 75 °C (167 °F) T4 : 95 °C (203 °F) T3 : 95 °C (203 °F) T2 : 95 °C (203 °F) T1 : 95 °C (203 °F)
Maximum values of the valve circuitThe value applies to each valve circuit. A cable length of 10 m is considered.
Voltagemax. 32 V
Currentmax. 240 mA
Internal capacitancemax. 10 nF
Internal inductancemax. 20 µ,H
Equipment protection level Mb
Type of protectionintrinsic safety
CE marking[*PD-Z02585A*]
Certificates
Appropriate typePL...-F25...-N4...
IECEx certificateIECEx TUN 17.0021X
IECEx markingEx ia I Mb
StandardsIEC 60079-0:2011 , IEC 60079-11:2011
Effective internal capacitancemax. 100 nF The value is applicable for one sensor circuit. A cable length of 10 m is considered.
Effective internal inductancemax. 100 µ,H The value is applicable for one sensor circuit. A cable length of 10 m is considered.
Maximum permissible ambient temperatureAlso observe the maximum permissible ambient temperature stated in the general technical data. Keep to the lower of the two values. at Ui = 15 V , Ii = 25 mA , Pi = 34 mW : 100 °C (212 °F) at Ui = 15 V , Ii = 25 mA , Pi = 64 mW : 100 °C (212 °F) at Ui = 15 V , Ii = 52 mA , Pi = 169 mW : 95 °C (203 °F)
Maximum values of the valve circuitThe value applies to each valve circuit. A cable length of 10 m is considered.
Voltagemax. 32 V
Currentmax. 240 mA
Internal capacitancemax. 10 nF
Internal inductancemax. 20 µ,H
General information
Use in the hazardous areasee instruction manuals