Inductive sensor FJ7-N x23GxxxD Pepperl+Fuchs 306134
Inductive sensor FJ7-N x23GxxxD Pepperl+Fuchs 306134

We are not the manufacturer, authorised distributor or authorised representative of the Pepperl+Fuchs brand in Australia. The private labels and part numbers shown on this website are the property of their respective owners.

Pepperl+Fuchs FJ7-N x23GxxxD 306134

Manufacturer

Pepperl+Fuchs

Country

Germany

Name

FJ7-N x23GxxxD

Part number

306134

Type

Inductive sensor

Description

Inductive sensor FJ7-N

Stock availability:

On request

221.4 €

Need cheaper?

Several positions are needed?

Send your request on email:

Worldwide delivery services:
fedex dhl ups
Ways of payment:
wire transfer paypal

Specifications FJ7-N x23GxxxD 306134

If you require FJ7-N x23GxxxD 306134 from manufacturer Pepperl+Fuchs, please contact FAMAGA.

For more than 8 years our employees supply repair parts for the upgrade and maintenance of various types of technical equipment from all corners of the earth. Over 750 orders from clients from various countries are arrived daily. Developed partner network makes it possible to immediately implement order for Pepperl+Fuchs FJ7-N x23GxxxD, while the client does not have to worry about extra costs.

Geography of deliveries involves Europe, America, Asia and Africa. There is no restrictions on the size and mass of the cargo. We developed different delivery options so that a buyer can choose suitable balance between cost and delivery time.

Company`s main postulate is transparency, which includes every segment of activity. Buyers get top-class spare parts and equipment, to which all necessary certificates are available. All repair parts and equipment are original, likelihood of counterfeits are excluded. For permanent customers there are bonus programs and they are valid affordable prices.

Become a customer from FAMAGA, get equipment with no delay and at beneficial price. Fill in data in the order form on the website. Our specialist will contact you to discuss nuances. Orders are also accepted by phone.

Features FJ7-N x23GxxxD 306134

General specifications
Switching functionNormally closed (NC)
Output typeNAMUR
Rated operating distance7 mm
Installationflush
Assured operating distance0 ... 5.67 mm
Reduction factor rAl 0.4
Reduction factor rCu 0.3
Reduction factor r304 0.85
Output type2-wire
Nominal ratings
Nominal voltage8.2 V (Ri approx. 1 k&Omega,)
Operating voltage5 ... 25 V
Switching frequency0 ... 200 Hz
Hysteresistyp. %
Current consumption
Measuring plate not detected&ge, 3 mA at nominal voltage
Measuring plate detected&le, 1 mA at nominal voltage
Switching state indicatorLED, yellow
Functional safety related parameters
MTTFd4080 a
Mission Time (TM)20 a
Diagnostic Coverage (DC)0 %
Compliance with standards and directives
Standard conformity
NAMUREN 60947-5-6:2000
StandardsEN 60947-5-2:2007 EN 60947-5-2/A1:2012 IEC 60947-5-2:2007 IEC 60947-5-2 AMD 1:2012
Approvals and certificates
FM approval
Control drawing116-0165
CCC approvalCCC approval / marking not required for products rated &le,36 V
Ambient conditions
Ambient temperature-25 ... 100 °C (-13 ... 212 °F)
Mechanical specifications
Connection typecable PUR , 2 m
Core cross-section0.34 mm2
Housing materialbrass, zinc plated
Sensing facePOM
Degree of protectionIP67
Cable
Bending radius> 10 x cable diameter
Data for application in connection with hazardous areas
Equipment protection levelGb , Gc (ic) , Mb
Equipment protection level Gb
Type of protectionintrinsic safety
CE marking[*PD-Z02585A*]
Certificates
Appropriate typeFJ7-N...
ATEX certificatePTB 00 ATEX 2032 X
ATEX marking II 2G Ex ia IIC T6&hellip,T1 Gb
StandardsEN 60079-0:2012+A11:2013 , EN 60079-11:2012
IECEx certificateIECEx PTB 11.0021X
IECEx markingEx ia IIC T6...T1 Gb
StandardsIEC 60079-0:2011 , IEC 60079-11:2011
Effective internal capacitancemax. 65 nF A cable length of 10 m is considered.
Effective internal inductancemax. 220 µ,H A cable length of 10 m is considered.
Maximum permissible ambient temperatureAlso observe the maximum permissible ambient temperature stated in the general technical data. Keep to the lower of the two values. at Ui = 16 V , Ii = 25 mA , Pi = 34 mW , T6 : 73 °C (163.4 °F) T5 : 88 °C (190.4 °F) T4 : 100 °C (212 °F) T3 : 100 °C (212 °F) T2 : 100 °C (212 °F) T1 : 100 °C (212 °F) at Ui = 16 V , Ii = 25 mA , Pi = 64 mW , T6 : 73 °C (163.4 °F) T5 : 88 °C (190.4 °F) T4 : 100 °C (212 °F) T3 : 100 °C (212 °F) T2 : 100 °C (212 °F) T1 : 100 °C (212 °F) at Ui = 16 V , Ii = 52 mA , Pi = 169 mW , T6 : 62 °C (143.6 °F) T5 : 77 °C (170.6 °F) T4 : 81 °C (177.8 °F) T3 : 81 °C (177.8 °F) T2 : 81 °C (177.8 °F) T1 : 81 °C (177.8 °F) at Ui = 16 V , Ii = 76 mA , Pi = 242 mW , T6 : 54 °C (129.2 °F) T5 : 63 °C (145.4 °F) T4 : 63 °C (145.4 °F) T3 : 63 °C (145.4 °F) T2 : 63 °C (145.4 °F) T1 : 63 °C (145.4 °F)
Equipment protection level Gc (ic)
Type of protectionintrinsic safety
CE marking[*PD-Z02586A*]
Certificates
ATEX certificatePF 13 CERT 2895 X
ATEX marking II 3G Ex ic IIC T6&hellip,T1 Gc
StandardsEN 60079-0:2012+A11:2013 , EN 60079-11:2012
Effective internal capacitancemax. 65 nF A cable length of 10 m is considered.
Effective internal inductancemax. 220 µ,H A cable length of 10 m is considered.
Maximum permissible ambient temperatureAlso observe the maximum permissible ambient temperature stated in the general technical data. Keep to the lower of the two values. at Ui = 20 V , Ii = 25 mA , Pi = 34 mW , T6 : 73 °C (163.4 °F) T5 : 88 °C (190.4 °F) T4 : 100 °C (212 °F) T3 : 100 °C (212 °F) T2 : 100 °C (212 °F) T1 : 100 °C (212 °F) at Ui = 20 V , Ii = 25 mA , Pi = 64 mW , T6 : 73 °C (163.4 °F) T5 : 88 °C (190.4 °F) T4 : 100 °C (212 °F) T3 : 100 °C (212 °F) T2 : 100 °C (212 °F) T1 : 100 °C (212 °F) at Ui = 20 V , Ii = 52 mA , Pi = 169 mW , T6 : 62 °C (143.6 °F) T5 : 77 °C (170.6 °F) T4 : 81 °C (177.8 °F) T3 : 81 °C (177.8 °F) T2 : 81 °C (177.8 °F) T1 : 81 °C (177.8 °F) at Ui = 20 V , Ii = 76 mA , Pi = 242 mW , T6 : 54 °C (129.2 °F) T5 : 63 °C (145.4 °F) T4 : 63 °C (145.4 °F) T3 : 63 °C (145.4 °F) T2 : 63 °C (145.4 °F) T1 : 63 °C (145.4 °F)
Equipment protection level Mb
Type of protectionintrinsic safety
Certificates
Appropriate typeFJ7-N...
IECEx certificateIECEx PTB 11.0021X
IECEx markingEx ia I Mb
StandardsIEC 60079-0:2011 , IEC 60079-11:2011
Effective internal capacitancemax. 65 nF A cable length of 10 m is considered.
Effective internal inductancemax. 220 µ,H A cable length of 10 m is considered.
Maximum permissible ambient temperatureAlso observe the maximum permissible ambient temperature stated in the general technical data. Keep to the lower of the two values. at Ui = 16 V , Ii = 25 mA , Pi = 34 mW : 100 °C (212 °F) at Ui = 16 V , Ii = 25 mA , Pi = 64 mW : 100 °C (212 °F) at Ui = 16 V , Ii = 52 mA , Pi = 169 mW : 81 °C (177.8 °F) at Ui = 16 V , Ii = 76 mA , Pi = 242 mW : 63 °C (145.4 °F)
General information
Use in the hazardous areasee instruction manuals